Home    Liquid cooling    Liquid cooling test equipment    L10 & L11 Flushing and Filling Equipment

L10 & L11 Flushing and Filling Equipment

This equipment is specially designed for liquid filling and flushing of liquid-cooled servers (L10) and liquid-cooled cabinets (L11) prior to testing.
Contact Us

Details

This equipment is specially designed for liquid filling and flushing of liquid-cooled servers (L10) and liquid-cooled cabinets (L11) prior to testing. It supports simultaneous filling and flushing for two cabinets or two nodes. The system integrates turbidity, pH, and conductivity sensors, along with a 25 μm precision filter, enabling real-time water quality monitoring. It adopts a dual-pump redundant configuration with variable frequency control, ensuring high reliability. The maximum flow rate reaches 324 L/min, with a control accuracy of ±1%, meeting diverse cleaning and flushing requirements. The equipment is powered by a Siemens PLC control system. Test duration and judgment criteria can be flexibly configured according to different product types. It is equipped with a 7-inch touchscreen and a 12.1-inch LCD display for real-time monitoring of test parameters and result evaluation. An integrated industrial PC with pre-installed upper-level control software enables communication with client ATE systems via a standard RJ45 interface. The default communication protocol is Modbus TCP/IP.

 

PRODUCT FEATURES:

Dual-channel design, supporting simultaneous cleaning and liquid filling for two cabinets or two nodes;

Supply and return ports with chuck-type or quick-connect fittings for easy assembly and maintenance;

SUS304 stainless steel piping design;

Integrated water quality monitoring with real-time measurement of pH, turbidity, and conductivity;

Equipped with 7-inch and 12.1-inch displays for convenient data reading and parameter configuration;

Supports PLC and upper-level computer control, integrating pressure, temperature, and humidity monitoring;

Built-in alarm system to assist maintenance personnel in quickly and accurately locating system abnormalities.

 

 

L10&L11 FLUSHING AND FILLING EQUIPMENT TECHNICAL SPECIFICATION:

L10 & L11 Flushing and Filling Equipment

Dimensions (H x W x D) mm

1650x800x1400

Application Target  

Liquid-cooled Cabinets (L10) or Liquid-cooled Servers (L11)

Channel Configuration

2  Channels

Operating Conditions

Input Voltage

3P/AC380V~480V/50&60Hz

Max. Power Consumption

5KW

Applicable Liquid Type

DI Water / PG25(Optional)

Flow Rate

Rack: 40-162 LPM

Node: 1-20 LPM

Filling Time (Adjustable)

Rack: ≤ 5 minutes/Rack, Node: ≤ 2 minute/Node

Flushing Time (Adjustable)

Rack: 30 minutes/Rack, Node: 5 minute/Node

Purging Time

Rack: 5 minutes/Rack, Node: 1 minute/Node

Fluid Quality Standard

DI Water:

Inlet: Conductivity: ≤3μs/cm, pH: 5-7.5,

Turbidity: <3NTU

Outlet: Conductivity: ≤10μs/cm, pH: 5-75,

Turbidity: <10NTU

PG25 Solution:

Inlet: Conductivity: ≤3000μs/cm, pH: 5-7.5,

Turbidity: <3NTU

Outlet: Conductivity: ≤5000μs/cm, pH: 8-10,

Turbidity: <10NTU

Filling Acceptance Criteria

Flow Rate & Cycle Time

Available Head (psi/ bar)

36.3/2.5

Solution Tank Capacity

160L

Wastewater Tank Capacity

160L

Optional External Solution Tank Capacity

1000L

Filter Accuracy

≤25μm

Design Pressure(psi/bar)*2

116/8

Test Pressure(psi/bar)

145/10

Net Weight (kg/lbs)

1000/2200

Operating Temp.(T&H)

-20-45℃/ RH 5-85%

Storage Temp.(T&H)

-40-65℃/RH 5-95%

Interface Specification

Air Supply: 3/4" Chuck-Type Connector (OD 50.5 mm)

Compressed Air: 1" Chuck-Type Connector (OD 50.5 mm)

Cabinet Inlet/Outlet: 1" Chuck-Type Connector (OD 50.5 mm)

Node Inlet/Outlet: UQD04 Male Connector

Power Connector

Aviation connector WS40J5Z

Communication Interface

2*RS485, 2* RJ45

Communication Protocol

Modbus TCP & Modbus RTU

Noise Level

72dB(A)

Appearance Color

RAL9005RAL9003